HDPE Pin Type Insulators
Introduction Victor's History Product Benefits Product Characteristics Cross Reference
|
CAT NO. |
NECK |
CANTILEVER STRENGTH (lbs.) |
TYPICAL APPLICATION VOLTAGES (kV) |
60 Hz FLASHOVER (kV) |
IMPULSE FLASHOVER (kV) |
60 Hz PUNCTURE VOLTAGE (kV) |
RADIO INFLUENCE VOLTAGE (MAX MICROVOLTS @ 1,000 kHz) |
|||
|
DRY |
WET |
POS |
NEG |
TEST (kV) |
MAX ( µV) |
|||||
|
C |
3,000 |
15 |
84 |
43 |
123 |
207 |
210 |
10 |
50 |
|
|
F |
3,000 |
15 |
80 |
46 |
122 |
202 |
215 |
10 |
50 |
|
|
- |
3,000 |
15 |
94 |
46 |
141 |
176 |
195 |
10 |
50 |
|
|
F |
3,000 |
25 |
87 |
51 |
144 |
179 |
225 |
10 |
100 |
|
|
F |
3,000 |
25 |
87 |
51 |
144 |
179 |
220 |
10 |
100 |
|
|
- |
3,000 |
25 |
96 |
55 |
153 |
190 |
220 |
10 |
100 |
|
|
- |
3,000 |
25 |
96 |
55 |
153 |
190 |
220 |
10 |
100 |
|
|
F |
3,000 |
35 |
106 |
70 |
168 |
225 |
235 |
10 |
100 |
|
|
F |
3,000 |
35 |
106 |
70 |
168 |
225 |
230 |
10 |
100 |
|
|
- |
3,000 |
35 |
112 |
59 |
172 |
215 |
250 |
10 |
100 |
|
|
- |
3,000 |
35 |
112 |
59 |
172 |
215 |
250 |
10 |
100 |
|
|
*-2 DESIGNATES 1 3/8" PINHOLE, ALL OTHERS ARE 1" PINHOLES. |
||||||||||
|
MINIMUM RECOMMENDED PIN HEIGHT OF 7 1/2" |
||||||||||
Click on Catalog Number in above table to obtain drawings of each insulator.
Ordering, Pricing, Technical Information
To place an order for Victor HDPE Pin Types or to obtain technical information about these products, drawings, pricing information, etc. please contact the factory. Lead times are available on this site, but for unusually large or small quantities or non standard packaging or colors please consult the factory.
Home | Lead Times | Products | Contact Us